中文十次啦,亚洲综合图片色婷婷另类小说,久久频这里精品香蕉久久,青青草国产精品视频,亚洲自拍 AV天堂,亚洲国产AV日韩AV二区色欲,亚洲日韩AV中文字幕免费

PRODUCT CENTER
IP6000d

IP6000 series flameproof positioner is mounted on pneumatic actuators. It's used to control air intake and exhaust of the pneumatic actuators to drive the valve position to the set point by calculating both data from 4-20mA DC signal and feedback position.

  • Easy to install, one-key auto-tune calibration
  • Mature and reliable piezo module, imported from Germany
  • Numerous functions can be activated(e.g. characteristic curves and limits)
Technical specification
Technical data
Mechanical Dimensions
Structure
Electrical connections
Pneumatic connections
Wiring diagram
Principle block diagram
Mounting components
Combination mode
  • Installation type
    Acting type
    Explosion proof
    Feedback signal
    HART
    Mounting kit & lever
    Pressure gauge
    Power off state
    Min. ambient temp

    Normal linear(L

    Remote linear*(FL

    Normal rotary(R

    Remote rotary*(FR

    Separate*(S

    Single acting(S

    Double acting(D

    Ex db IIC T6 Gb;Ex tb IIIC 85℃ Db(d

    Ex db I Mb(k

    No(0

    Yes(1

    No(0

    Yes(1

    No(0

    Linear(1

    Rotary(2

    No(0

    Yes(1

    Safe(S

    Freeze(F

    -20℃(N

    -40℃(L

In the installation type options, the options marked with * (FL, FR and S) do NOT support explosion proof option d (Ex d IIC T6 Gb).
* marked option S (separate type) does NOT support the Min. ambient temperature option L (-40℃).

Technical Data

Enclosure material

Aluminum
Pressure gauge block material

Aluminum, anodized

Input signal

Input resistance: 120Ω   

Limit voltage: 28V

Output signal

Feedback type: 2-wire 4~20mA signal, internal resistance 120Ω

Digital communication protocol HART 7
Minimum operating current 3.8mA
Steady state air consumption ≤ 0.4 L/min
Stroke range

Default linear type: 10~100mm

Default rotary type: 30~100°

Separate type: 5~50mm

Optional mounting bracket: Hard connection or

soft connection

Note: The stroke range of remote type is the same

as that of default type


Pneumatic data

Air quality meets ISO 8573-1 standard

Pressure range:1.4~7bar(20.3~101.5psi)

Solid particle size and density: Grade 3

Pressure dew point: Class 3 (minimum 20K (36°F) lower than the ambient temperature)

Oil content: Class 3

Vibration resistance

0.15mm, 10Hz-60Hz, 20 cycle/axis 

20m/s2, 60Hz-500Hz, 20 cycle/axis Recommended range for control valve ≤20m/s2, no resonance peak

Electrical connection M20×1.5
Pneumatical connection G1/4
Protection class IP67

Basic error & Hysteresis error

≤ 1%
Ambient temperature

Ex d default type: -20 ℃ ~ +60 ℃(CCC),-20℃ ~ +40℃(EAC-T6)

Ex d low temperature type : -40℃ ~ +60 ℃(CCC),-55℃ ~ +40℃(EAC-T6)


Explosion-proof grade

Ex db Ⅰ Mb

Ex db ⅡC T6 Gb

Ex tb ⅢC T85℃ Db



Connection

Description
IN+

4-20 mA input signal +

IN-

4-20 mA input signal -

OUT+

Feedback signal module 18-30 V DC+

OUT-

Feedback signal module 4-20 mA output

Connection Description

SUP

Air supply input

OUT1

Pilot air outlet 1

OUT2    

Pilot air outlet 2


  • Ex d linear type
  • Ex d rotary type